Permit: T00CM02740

Parcel: 13314227B


Addresses:

1400 N WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T00CM02740

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2001 MECHANICAL - ABOVE CEILING Approved
12/29/2000 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
SUSPENDED ROUGH DUCTS ABOVE HARD LID OK
DROPS TO REGISTER WILL BE ADDED THROUGH OPENINGS FOR LIGHT FIXTURES
12/11/2000 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
INSPECTION ON CORRIDOR 138. OK TO CLOSE CEILING
12/08/2000 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
USE BREAKWAY JOINTS ON FIRE DAMPERS
INSTALL ACCESS DOORS FOR FIRE DAMPERS
CAP OFF ABANDONED DUCT IN CORRIDOR #138 AND PATCH DRY WALL 2 EACH
FIRE TAPE FIRE DAMPER OPENINGS
FINISH INSULATION HOT WATER PIPE AND BARE METAL ON DUCTS, VERIFIED PRESSURE TEST ON OXY, MED A, VAC. 200 PSI
CORRECT AND RECALL
INSTALL SMOKE DETECTORS IN DUCTS