Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2001 | MECHANICAL - ABOVE CEILING | Approved | ||
| 12/29/2000 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* SUSPENDED ROUGH DUCTS ABOVE HARD LID OK DROPS TO REGISTER WILL BE ADDED THROUGH OPENINGS FOR LIGHT FIXTURES |
|
| 12/11/2000 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* INSPECTION ON CORRIDOR 138. OK TO CLOSE CEILING |
|
| 12/08/2000 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* USE BREAKWAY JOINTS ON FIRE DAMPERS INSTALL ACCESS DOORS FOR FIRE DAMPERS CAP OFF ABANDONED DUCT IN CORRIDOR #138 AND PATCH DRY WALL 2 EACH FIRE TAPE FIRE DAMPER OPENINGS FINISH INSULATION HOT WATER PIPE AND BARE METAL ON DUCTS, VERIFIED PRESSURE TEST ON OXY, MED A, VAC. 200 PSI CORRECT AND RECALL INSTALL SMOKE DETECTORS IN DUCTS |