Permit: T00CM02698

Parcel: 129041290


Addresses:

19 N NORRIS AV #02


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T00CM02698

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/16/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/15/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/1. GAS PACK CONDENSATION LINE CANNOT BE INSTALLED BY DRILLING ABS WASTE VENT. INSTALL A SANITARY T AND REDUCER ON WASTE VENT FOR CONDENSATE CONNECTION. ELECTRIC GFCI OUTLET LEFT OF SINK WIRED INCORRECTLY HOT WHEN TRIPPED.
02/14/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*
02/12/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*