Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/18/2000 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 07/25/2000 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/PLUMBING PLAN NEEDS TO BE REVISED TO SHOW LAUDRY TUB AND DELETION OF DRYER. ADDED TO PLUMBING SCHEMATIC, ON SHEET A1, CONTRACTOR CONTINUE AT OWN RISK PENDING REVISIONS. ALL ROUGH ABS INCLUDING LAUDRY SINK UP TO N/E CORNER OF HOUSE APPROVED FOR TEST. (AT CLEAN OUT). |
| 07/24/2000 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/1. NO WATER TEST ON DRAIN SYSTEM. MUST HAVE A MINIMUM OF 42" WATER COLUMN ABOVE F.F. 2. LAUNDRY DRAIN MUST BE A MINIMUM OF 12" BELOW GRADE. |