Permit: T00CM02628

Parcel: 103080040

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/26/2000 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
09/19/2000 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*
08/29/2000 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. PROVIDE DETAIL 12/53.1 AT GARAGE DOOR ENTRY, BOTH SIDES. 2. ALL SHEAR PANELS MUST GO FROM SOLE PLATE TO ROOF DIAPHRAM--COMPLETE SHEATING 2326.11.3. 3. ALL ALTERNATE PANELS CAN NOT EXCEED 10'-0" AND SHALL CONNECT TO ROOF DIAPHRAM SEC.UBC--2326.11.4. 4. BEAM AT GARAGE ENTRY NEED TO BE TIED HORIZONTALLY BOTH SIDES AT TOP.
08/25/2000 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/SAME AS 8-24-00
08/24/2000 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. BRACED WALL PANELS MUST EXTEND FROM BOTTOM TO TOP PLATES MANY NOT IN. 2. HOLD DOWNS NOT NAILED. 3. WALLS NOT CLIPPED 4. HEADERS AND KING STUDS NOT CLIPPED 5. DOUBLE TOP PLATE SPLICES CANNOT BE WITHIN 48" OF EACH OTHER.
08/21/2000 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection CANCELLED