Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/26/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 09/19/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/29/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/1. PROVIDE DETAIL 12/53.1 AT GARAGE DOOR ENTRY, BOTH SIDES. 2. ALL SHEAR PANELS MUST GO FROM SOLE PLATE TO ROOF DIAPHRAM--COMPLETE SHEATING 2326.11.3. 3. ALL ALTERNATE PANELS CAN NOT EXCEED 10'-0" AND SHALL CONNECT TO ROOF DIAPHRAM SEC.UBC--2326.11.4. 4. BEAM AT GARAGE ENTRY NEED TO BE TIED HORIZONTALLY BOTH SIDES AT TOP. |
| 08/25/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/SAME AS 8-24-00 |
| 08/24/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/1. BRACED WALL PANELS MUST EXTEND FROM BOTTOM TO TOP PLATES MANY NOT IN. 2. HOLD DOWNS NOT NAILED. 3. WALLS NOT CLIPPED 4. HEADERS AND KING STUDS NOT CLIPPED 5. DOUBLE TOP PLATE SPLICES CANNOT BE WITHIN 48" OF EACH OTHER. |
| 08/21/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
CANCELLED |