Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/06/2001 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 03/02/2001 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ALL OK BUT LAVS. 1. LAVATORIES NOT PROPERLY PLUMBED : 1/4 BENDS NOT ALLOWED IN HORIZONTAL DRAIN LINES, SANITARY "T" FITTINGS NOT ALLOWED IN HORIZONTAL DRAIN LINES, TWO FIXTURES CANNOT DRAIN INTO A SINGLE TRAP ARM, TRAP ARMS EXCEED 42" TO VENTS. |