Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS RECONNECT
Permit Number - T00CM02464
Inspection Description - PLUMBING - GAS RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2000 | PLUMBING - GAS RECONNECT | Approved | IVRS - Inspection 0000* | |
11/29/2000 | PLUMBING - GAS RECONNECT | Denied | IVRS - Inspection 0999*/CONFERENCE-NO CHANGE. | |
11/17/2000 | PLUMBING - GAS RECONNECT | Denied | IVRS - Inspection 0999*/1. WATER HEATER "B" VENT CANNOT BE WITHIN 1" OF COMBUSTABLES. 2. NORTH EAST HALL BATHROOM LAV ABS TO GALVANIZED NO HUB CONNECTION WAS NOT PROPERLY INSTALLED. EXPOSE. 3. WATER HEATER SINGLE WALL VENT CANNOT BE WITHIN 6" OF COMBUSTABLE MATERIAL. 4. WATER HEATER "B" VENT CANNOT BE IN STAIRWELL WITHIN 6'6" OF STEP RISERS. 5. CANNOT APPROVE GAS RECONNECT UNTIL ALL APPLIANCES ARE CONNECTED. 6. W/H "B" VENT INSTALLED UPSIDE DOWN. | |
11/08/2000 | PLUMBING - GAS RECONNECT | Not ready for Inspection | IVRS - Inspection 0000* |