Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM02461
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2000 | FRAMING | Approved | IVRS - Inspection 0000* | |
11/16/2000 | FRAMING | Denied | IVRS - Inspection 0999*/1. SUPPORT GAS LINE AT LAUNDRY. 2. REPAIR ALL EXHAUST 3. COMPLETE FRAMING AT LAUNDRY. 4. PROVIDE 16" O.C. FIRE FRAME AT GARAGE MECHANICAL. 5. CLIP LIVE SOFFITS 1ST AND 2ND FLOOR. 6. STRAP CEILING DROP IN KITHCEN 32" O.C. 7. FIRE BLOCK OUTSIDE MECHANICAL RM. 8. PROVIDE 1" CLEARANCE AT ALL FLUES, PROVIDE HOT WATER FLUE. 9. SUPPORT 90 DEGREE VTR. 10. BLOCK A/C 3 SIDES 2ND LEVEL. 11. PROVIDE 6'-8" CLEARANCE STAIR LANDING. |