Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
Permit Number - T00CM02416
Inspection Description - PLUMBING - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* | |
08/22/2000 | PLUMBING - FINAL | Denied | OK FOR TEMP C OF NEED THESE CHANGES FOR FINAL MEN'S BATHROOM 12" MIN AND TO PARTITION ON URINAL MIN 30" FOR HANDICAPPED LAVATORY WOMENS BATHROOM 15" MINIMUM FROM AND OF W C TO SIDEWALL OR OBSTRUCTION HANDICAPPED WATTER CLOSET MIN 17" AFF HANDICAPPED LAVATORY NEEDS INSULATION KIT |