Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM02416
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* DIST GUTTERS IN VIOL OF 110-26 DIST GUTTLER #4 AT EXTERIOR FOREIHN PIPING SEWER DRAIN AND WATER PIPING ABOVE ELECTRICAL EQUIPMENT DOUBLE LUGGING INCOMPLETE DOUBLE LUGGING AT T-11 DISCONNECT STRAP GROUND WIRE AT T-1 TEM C OF O WILL BE OK MUST HAVE APPROVED APPEAL ON HAND |
|
08/10/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* ALL ELECTRICAL WORK IE. EQUIPMENT/TO BE WIRED BY C-11 CONTRACTOR NEED U.L. OR EQUIVALENT IISTING ON ALL EQUPMENT CLEARANCE PER 110-26 NEED TO BE FOLLOWED LOOSE FITTING IMPROPER FITTING 250-97 |