Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM02265
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
03/01/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* ADDED ROOF DRAIN S.W. CORNER. I WILL CHECK ON REVISED PLANS | |
02/23/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) 1ST FLOOR S. W. DOUBLE BATHROOM N/H DWV OK WATER TEST OK 2) COPPER OK PRESSURE TEST OK 3) OK TO COVER WALLS | |
02/22/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) S.E. BATHROOM 2ND FLOOR 2) N/H DWV OK WATER TEST OK 3) COPPER OK PRESSURE TEST OK 4) OK TO COVER WALLS 5) FLOOR DRAINS OK |
|
02/16/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) NORTH WEST SECOND FLOOR BATHROOMS DWV OK WATER TEST OK 2) COPPER OK PRESSURE TEST OK 3) 2ND FLOOR 4 BLDG DRAIN OK TO TIE-IN AT BLDG SEWER |
|
02/08/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* WATER HCS BLDG WATER SUPPLY 4" COPPER AT BLDG TRANSITION WITH FLANGE TO C 900 PVC UNDERGROUND THEN BACK TO COPPER AT METER NEED TO SEE TIE IN AT METER PRESSURE TEST TO 150# OK OK TO COVER BACKWATER VALVE PIT AND COVER OK EAST WING BATHROOMS FIRST FLOOR N/H OK WATER TEST OK COPPER OK PRESSURE TEST OK OK TO COVER FIRST FLOOR WALLS ONLY |
|
02/07/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* ROOF DRAINS, 14 SETS, DRAINS AND OVERFLOWS OK WATER TEST OK OK TO COVER WHERE APPLICABLE OVERFLOW SCUPPERS OK NEED TO SEE ROOF DRAIN EXTENSION, PAST BLDG |
|
02/05/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) 4TH FLOOR DRAINS IN BATHROOMS OK. OK TO COVER. 2) JANITORS SINK NORTH WING OK | |
01/26/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* FIRST FLOOR NORTH WING BATHROOMS OK DWV N/H OK WATER TEST OK COPPER OK PRESSURE TEST OK T&P DRAIN OK TRAP PRIMES OK RECIRC LINE OUT OF BATHROOM OK OK TO COVER WALLS |
|
01/25/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* NORTH WING 1ST FLOOR BATHROOM OK TO COVER ONE SIDE |