Permit: T00CM02257

Parcel: 11205052B


Addresses:

3180 N CAMPBELL AV


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T00CM02257

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2001 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
03/20/2001 MECHANICAL - ABOVE CEILING Partial Approval 1) RETAINING ANSLES ON REAR SIDE OF FIRE / SMOKE DAMPERS DO NOT HAVE FULL CORNERS
2) WHEN COMPLETE INSULATE SHEET METAL FITTINGS TO CARRY COOLING CONTINOUSLY
3) LEAVE TILES OUT AT DAMPER TO CHECK CORRECTIONS OK TO COVER BALANCE