Permit: T00CM02250

Parcel: 118037990

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
11/03/2000 BUILDING - FINAL Approved IVRS - Inspection 0000*
11/01/2000 BUILDING - FINAL Denied IVRS - Inspection 0999*/1. NO PART OF A FLEX CONNECTION MAY ENTER THE FURNACE CAVITY. 2. REMOVE ELECTRIC LINE WITHIN ATTIC ACCESS. 3. PROVIDE MIN 3 SCREWS AT FLUE CONNECTION. 4. GAS LINE NOT SUPPORTED.
10/31/2000 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/1. PROVIDE PERMANENT ATTACHMENT OF GAS RISER TO HOUSE. (PARALELL EXTENSION). 2. COMPLETE STUCCO REPAIR AT EXHAUST HOOD VENT. 3. PROVIDE PLASTIC TO ACCESS HOUSE FIELD CONDITIONS EXCESSIVELY MUDDY.
10/27/2000 BUILDING - FINAL Denied IVRS - Inspection 0999*/1. YARD WATER SHUT OFF NOT ACCESSIBLE. 2. PROVIDE SECURE ATTACHMENT FOR GAS EXTENSION AND PROVIDE TEST, (MIN. 10 PSI.) 3. RANGE EXHAUST HOOD NOT SEALED EXTERIOR. 4. FURNACE FLUE NOT COMPLETE. 5. GUARD RAIL AT SECOND STORY BALCONY NOT SECURE. 6. PROVIDE ATTIC ACCESS.