Permit: T00CM02246

Parcel: 13707046D


Addresses:

205 W IRVINGTON RD

Inspection Status: Partial Approval

Inspection History: PLUMBING - PROGRESS

Date Description Inspector Results Comments
04/12/2001 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000* CONDENSATE DRAIN LINE, CU ZYPEL?, RUN UNDER BRICK AS PER PLAN, OK TO COVER
03/30/2001 PLUMBING - PROGRESS Partial Approval 1) SOUTH SIDE COOLER WATERS CORRECTION FROM PVC TO COPPER OK ON SOUTH SIDE OF COMPLEX
2) PRESSURE TEST OK 3) OK TO COVER
03/29/2001 PLUMBING - PROGRESS Denied IVRS - Inspection 0999* 1) AGAIN PVC MAY NOT BE USED IN THE AREAS YOU HAVE INSTALLED IT. PLEASE PROVIDE REVISED APPROVED DRAWINGS, SHOWING APPROVED MATERIALS AND ROUFING OF APPROVED MATERIALS
03/28/2001 PLUMBING - PROGRESS Denied IVRS - Inspection 0999* 1) PLANS SHOW PVC UNDER SLAB, UNDER PAVERS, AND UNDER STRUCTURES. PLEASE REVIEW IAPMO INSTALLATION STANDARD IS 8-92 IS 8-92 313.4 PVC MAY EXTEND ONLY 24" ABOVE GRADE PLEASE REVIEW IS 8-92 604.1 LOCATION OF PVC PIPE