Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - PROGRESS
Permit Number - T00CM02246
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2001 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection 0000* CONDENSATE DRAIN LINE, CU ZYPEL?, RUN UNDER BRICK AS PER PLAN, OK TO COVER | |
| 03/30/2001 | PLUMBING - PROGRESS | Partial Approval | 1) SOUTH SIDE COOLER WATERS CORRECTION FROM PVC TO COPPER OK ON SOUTH SIDE OF COMPLEX 2) PRESSURE TEST OK 3) OK TO COVER |
|
| 03/29/2001 | PLUMBING - PROGRESS | Denied | IVRS - Inspection 0999* 1) AGAIN PVC MAY NOT BE USED IN THE AREAS YOU HAVE INSTALLED IT. PLEASE PROVIDE REVISED APPROVED DRAWINGS, SHOWING APPROVED MATERIALS AND ROUFING OF APPROVED MATERIALS | |
| 03/28/2001 | PLUMBING - PROGRESS | Denied | IVRS - Inspection 0999* 1) PLANS SHOW PVC UNDER SLAB, UNDER PAVERS, AND UNDER STRUCTURES. PLEASE REVIEW IAPMO INSTALLATION STANDARD IS 8-92 IS 8-92 313.4 PVC MAY EXTEND ONLY 24" ABOVE GRADE PLEASE REVIEW IS 8-92 604.1 LOCATION OF PVC PIPE |