Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/03/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* 480V TRANSFORMER/PANEL BOARD COMBO UNIT MOUNTED AT APROX. 70 DEGREES AT 13FT HEIGHT IS IN VIOLATION OF NEC 110-26 (DOOR LESS THAN 90 DEGREE OPENING AND 90-4) |