Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/20/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/18/2000 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ATTIC FURNACE REVISION PER R AIELLO |
| 08/02/2000 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/PENDING FURNACE'S IN ATTIC REVISION. |
| 08/01/2000 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/OK TO INSULATE. |
| 07/31/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. APPROVE ATTIC VENTING PER SHEET A-5. 2. PROVIDE BRACING PER TRUSS CALC'S--SEE WEB BRACING. 3. PROVIDE STRAPS AT DOUBLE TOP PLATE (2 PLACES) INTERIOR BEARING. 4. PROVIDE TYPE "B" FLUE PIPE FOR HOT WATER TANK. 5. SUPPORT 90 DEGREES UTR THROUGH HOUSE. 6. STRAP ALL GAS LINES THROUGH OUT HOUSE PER UPC 12.2 TABLE. 7. PROVIDE MIN. ATTIC ACCESS PER LINE 908- |
| 07/12/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0165*/THE CHANGE OF TRUSSES FROM THE BCI-LUL TRUSSES SPECIFIED ON PLAN TO THE "SLOPING FLAT" TRUSSES REQUIRES A REVISED DRAWING, PREPARED BY THE ARCHITECT OF RECORD, BE SUBMITTED FOR REVIEW AND APPROVAL OF CITY OF TUCSON PLANS REVIEWER. THE TRUSS CHALC'S MUST ALSO BE CITY APPROVED AND STAMPED. |
| 07/07/2000 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |