Permit: T00CM02218

Parcel: 12111012A


Addresses:

5010 E BELLEVUE ST

Inspection Status: Correction Required

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/23/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - 1. CONDENSATE MAY NOT TERMINATE INTO AN 1 1/2 VENT. MUT BE 2 MIN. 2. YOU MUST USE AN APPROVED FITTING WHEN TERMINATING INTO THE SIDE OF A VENT 3. NEED TO SEE A PERMIT AND PRESSURE TEST ON THE NEW GAS LINE INSTALLED. 4. REPLACE THE STEEL STRAP ON COPPER LINE.
05/23/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*