Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/21/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/01/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) UPDATE OR INSTALL PANEL SCHEUDLES ALL UNITS. 2.) BOXES OR RECEPTACLES NOT INSTALLED PROPERLY IN BATHROOM AND OUTSIDE OUTLETS. 3.) COMPLETE INSTALLATION OF CAN LIGHTS RECEPTACLES ALL UNITS. 4.) GFCI RECEPTACLES NOT TRIPPING PROPERLY WHEN TESTED ALL UNITS. 5.) IMPROPER ROMEX CONNECTORS AT TOP OF PANEL UNIT #1 6.) DISCONNECTS FOR AC UNITS IN VIOLATION OF WORKING CLEARANCE ALL UNITS. 7.) UNLOCK WATER HTR ROOMS TO CHECK CONNECTIONS. 8.) HAVE ELECTRICAL CONTR ACTOR CHECK OUT COMPLETE SYSTEMS EACH UNIT BEFORE RE-CALLING FOR FINAL. |
| 06/25/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |