Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/23/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. KITCHEN LAYOUT DOES NOT MATCH APPROVED PLAN (PROVIDE APPROVED REVISION) 2. ISLAND VENTING ONLY PERMITTED WHERE NOT POSSIBLE TO VENT THROUGH ROOF. 3. SHEARWALL AT BACK OF GARAGE NOT PER PLAN SEE 13/DI AND 17/01. 4. AIR REGISTERS MUST BE SUPPORTED (BLOCK 3 SIDES). 5. REFER LINES INCOMPLETE. 6. PEX LINES PENETRATING STEEL MUST BE PROTECTED. 7. AT KITCHEN HIP INSTERSECTION, ANCHOR GUSSET TO COMMON. 8. BRACE STUB TRUSSES PER 8/DI. 9. STUCCO MESH INCOMPLETE. |