Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM02164
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2001 | FRAMING | Approved | IVRS - Inspection 0000*/OK TO DRYWALL. | |
| 02/02/2001 | FRAMING | Denied | IVRS - Inspection 0999*/1. 8 STUDS ON EXTERIOR WALLS ARE NOT IN CONTACT OR BEARING ON SILL PLATE. 2. 2 FIRE BLOCKS MISSING MASTER B/R AT CEILING. | |
| 01/12/2001 | FRAMING | Denied | IVRS - Inspection 0950*/1. HOLD DOWNS MUST BE ATTACHED TO FULL LENGTH DOUBLE STUDS NOT CRIPPLES, TRIMMERS OR SINGLE STUDS. PROVIDE ENGINEERS APPROVED REPAIR FOR 5 LOCATIONS. 2. BLOCK TRUSSES AT BOTTOM CHORD PER 4/5. 3. NAILERS REQUIRE H3 CLIPS PER 6/5. 4. NO PRESSURE TEST ON PLUMBING AND LOW PRESSURE TEST ON GAS. 5 SECURE 4 SWITCH ELECT A.C. BOX ON 2 ENDS. 6. "0" CLEARANCE FIRE PLACE DAMAGED/CRUSHED. PROVIDE MANUFACTURES ENGINEER AND C.O.T. APPROVAL OF REPAIR OR REPLACE. 7. FIREPLACE VENT IMPROPERLY INSTALLED AND IN CONTACT WITH WOOD 8. REVERSE FLOW ON LAV TRAP ARM. 9. STUDS ON EXTERIOR WALLS MUST BEAR ON SILL PLATES. |