Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
12/03/2010 ELECTRIC - UNDERGROUND Approved
07/28/2000 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*
OK POLE BASE
1. NEED UNDERGROUND CONDUIT EXPOSED FULLY
07/26/2000 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*
1. UNDERGROUND NOT PREVIOUSLY INSPECTED IN PARKING LOT NEED TO BE EXPOSED FULLY FOR INSPECTION.
2. USE OF PVC FOR POLE BASE NOT ALLOWED PER PLANS USE GRS CONDUIT
07/24/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
1. NEED GRS CONDUIT IN POLE BASE OR LETTER FROM ENGINEER (AS PER PLAN) NOTE CHECK UNDERGROUND CLEARANCES