Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM02125
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TEMP POWER CONTINGENT ON POSTED BOND. OR FINAL APPROVAL OF ALL TRADES |
|
10/02/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* SOUTHWEST SERVICE 480V AND 120/208V PANELS MUST HAVE ENCLOSURES (CABINETES) GROUNDED OR BONDED BY BOND JUMPER OR GROUND SCREW THRU GROUND BARS TO METAL ENCLOSURE BOND NEUTRAL IN TRANSTORMER BOND WATER AND FIRE SPRINKLER PIPING SYSTEMS NORTH WEST SERVICE BOND BUSHING REQUIRED OR BONDING TYPE LOCKNUTS ON NIPPLE BETWEEN CT CAN AND METER BASE NEC 250-94 |
|
09/28/2000 | ELECTRIC - FINAL | Denied | INSTALL PERMANENT ADDRESS LABEL ON METER BASE ID BREAKER PANELS REMOVE DEAD FRONT ON BREAKER PANELS X-FORMER FOR INSPECTION 2" OFFSET NIPPLE NOT SEATED PROPERLY BETWEEN METER BASE AND PANEL. BOND BUSHING FEEDERS NOT CONNECTED IN CT CAN (SECONDARY) FEEDER NOT COLOR CODED |