Permit: T00CM02125

Parcel: 127090080


Addresses:

5975 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM02125

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TEMP POWER CONTINGENT ON POSTED BOND. OR FINAL APPROVAL OF ALL TRADES
10/02/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
SOUTHWEST SERVICE
480V AND 120/208V PANELS MUST HAVE ENCLOSURES (CABINETES) GROUNDED OR BONDED BY BOND JUMPER OR GROUND SCREW THRU GROUND BARS TO METAL ENCLOSURE
BOND NEUTRAL IN TRANSTORMER
BOND WATER AND FIRE SPRINKLER
PIPING SYSTEMS
NORTH WEST SERVICE
BOND BUSHING REQUIRED OR BONDING TYPE LOCKNUTS ON NIPPLE BETWEEN CT CAN AND METER BASE NEC 250-94
09/28/2000 ELECTRIC - FINAL Denied INSTALL PERMANENT ADDRESS LABEL ON METER BASE
ID BREAKER PANELS
REMOVE DEAD FRONT ON BREAKER PANELS X-FORMER FOR INSPECTION
2" OFFSET NIPPLE NOT SEATED PROPERLY BETWEEN METER BASE AND PANEL. BOND BUSHING FEEDERS NOT CONNECTED IN CT CAN (SECONDARY)
FEEDER NOT COLOR CODED