Permit: T00CM02100

Parcel: 12407190A


Addresses:

840 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T00CM02100

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/08/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000* CORRECTIONS HAVE BEEN MADE
02/07/2001 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
02/01/2001 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*
01/31/2001 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
BOND HAS BEEN POSTED FOR TEMP POWER OR GAS 19510352.1113BCM
WILL NEED PLAN REVISION AT TIME OF FINAL FOR GAS VALVE AND LOCATION OF ROOF DRAIN AND OVERFLOW DRAIN TERMINATION OK FOR TEMP C OF O
CORRECTIONS HAVE BEEEN MADE ON GAS TEST OK NEED APPROVED FROM FIRE BOND HAS BEEN POSTED
01/29/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*
FLEX CONNECTOR AT WATER HEATER TOO LONG SEE TABLE 12-10 94 UPC
SUPPORT GAS PIPING ABOVE CEILING PLEASE CHECK ALL OVERHEAD PIPE FOR MINIMUM STRAPPING
DRAIN FROM ICE MAKER NOT ACCEPTABLE
CHECK ALL AIR GAPS FOR MINIMUM CLEARANCE
INDIRECT WASTE PIPING 5'-15 NEEDS TO BE TRAPPED
INSULATE HOT WATER LINES
PROVIDE APPROVED DRAWINGS FOR ADDITION OF URINAL
PROVIDE APPROVED DRAWINGS FOR WATER HEATER RELOCATE
PROVIDE CERTIFICATION FOR BACK FLOW DEVICES
CHECK ALL WORK I DON'T MAKE PUNCH LISTS
01/29/2001 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
GAS REMOVE UNION PROVIDE RIGHT LEFT NIP CUP ANCHOR ALL WATER LINES PROVIDE 16 SIDE CLEARENCE PAINT CONDENSATE LINES SEE PLAN FOR APPROVED CONDENSATE LINES PVC SEE PLAN ON ROOF DRAINS EXTEND TO CURB INDIRECT WASTE LINES TESS ALL BACKFLOW DEVICES
01/25/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*
PLEASE HAVE PLUMBER REWIEW CONTRACT DOCUMENTS AND INSTALL PER PLAN
COMPLETE ALL WORK BEFORE CALLING IN FOR INSPECTION