Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/03/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*APPROVED FINAL POWER CLEARANCE SUBJECT TO LAST INSPECTOR. |
| 05/28/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1.) THE SERVICE ENTRANCE SWITCH GREAR MUST HAVE A PERMANENT ADDRESS ON OUTSIDE AS REQUIRED BY 99 NEC & CITY ORDINANCE 2.) PLAN SHOWS TA OFF PNL LA FED FROM 225A BKR RATHER THAN 175A SO DOES 2ND BUILDING. 3.) SEVERAL ITEMS HAVE BEEN DELETED FROM ORIGINAL PLANS APPARENTLY VALUE ENGINEERING HAS OMMITTED ITEMS SHOW ON PLAN PER OWNER. PLEASE PROVIDE A LETTER STATING OWNER HAS TAKEN THESE OPTIONS TO RELEASE ACTUAL PLAN FROM BEING FOLLOWED. |
| 05/22/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOT READY REVISIONS AND TORQUE LETTER NEEDED TRANS OK CK SUB PANEL TERMINATIONS ON GEAR OK CK PLAN TO REVISIONS. |
| 05/15/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PANELS ARE LOCKED I NEED ACCESS FOR INSPECTION. 2.) PLEASE PROVIDE REVISED CITY APPROVED PLANS FOR SERVICE TO REFLECT EQUIPMENT INSTALLED. THE LETTER DOES NOT PROVIDE ENOUGH INFORMATION. 3.) PROTECT PLACTIC FLOOR BOXES. 4.) PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD VERIFING TORQUE VALVES. |
| 04/22/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*SEE WRITE UP FOR BLDG #3. 1.) PLEASE PROVIDE A LETTER VERIFING TORQUE VALUES 2.) SERVICE PLAN CALL FOR 100AMP MAIN IN SECTION WITH GFP PROTECTION GFP. IS NEEDED AS PER CODE 230-95. 3.) PLEASE PROVIDE FUSE AS PER PLAN FOR EQUALS. 4.) BREAKERS NEED TO BE LABELED. 5.) BOND THE NEUTRAL AT TRANSFORMER 250-24. 6.) PLANS ARE NOT REFLECTIVE TO INSTALLED EQUIPEMENT. |