Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2001 |
SHEET ROCK NAILING |
|
Approved |
IVRS - Inspection 0000* |
| 03/08/2001 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0999* |
| 03/06/2001 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0999*/1. HAVE ENGINEER OF RECORD PROVIDE NAIL SIZE AND SPACING FOR BRACED WALL PANELS. A & C ON GROUND FLOOR AND 1 & 2 ON SECOND FLOOR. DO BRACED PANELS REQUIRE NAILS IN TOP & BOTTOM PLATES. HAVE REVISION APPROVED BY CITY OF TUCSON. 2. SHEAR WALL AT SECOND FLOOR MUST HAVE ALL ENDS AND EDGES BLOCKED AND NAILED AT 4" O.C. |