Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM02028
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR SUBJECT TO FINAL APPROVALS OTHER TRADES. | |
05/11/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) NO COMPLIANCE WITH PREVIOUS INSP WRITE UP #2, 3, & 5 2) A RE INSP FEE WILL BE ASSESSED NEXT INSP. IF NOT READY | |
05/01/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) BOND BUSHINGS OR BOND LOCKNUTS REQUIRED IN CT CAN (BOTH ENDS OF NIPPLES) 250-94 NEC 2) REMOVE PANEL COVERS, GUTTER COVER, FOR INSPECTION OF WIRING AND CONNECTIONS 3) INSTALL PANEL SCHEDULES 4) OUTDOOR GFCI RECEPTICLES BY IRRIGATION NEEDS W/P COVER 5) NEED TO VERIFY GAS BOND, GROUND RODS, UFER 250-104 |