Permit: T00CM02014

Parcel: 125171530


Addresses:

3840 E 5TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/28/2000 PLUMBING - GAS PRESSURE TEST Approved
09/20/2000 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection 0000*
GAS PRESSURE TEST OK
GAS SHUT OFF VALVES OK
ALL CORRECTIONS HAVE BEEN MADE
NOTE: WATER HEATER HAS NOT BEEN INSTALLED AT THIS TIME
CLOSET RINGS HAVE BEEN INSTALLED
09/13/2000 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*
MUST BRIND ENTIRE EXSISTING GAS SYSTEM
TO CODE
MUST HAVE MIN 1 1/2" CLEARANCE OF ROOF BLOCKS OR UNISTRUT
REMOVE ALL THREAD PROTECTORS AND UNIONS IN LINE
GAS SHUT OFF VALVES MUST BE MAX 3'0" FROM
APPLIANCE CONNECTION
RE TEST SYSTEM