Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/30/2000 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/17/2000 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999$/1. REAR STOOP. 2. BUSHING IN SERV PANEL. 3. BACK CHECK DEVICE AT HOSE BIB. 4. OUTLET IN BED HATS AN OPEN GRD. 5. ROOF JACKS ON ROOF PENETRATIONS. 6. T & P LINE TIED INTO CONDENSATE 7. MIN. SIZE ROOF VENT IS 2" USE CORRECT FITTING FOR CONDENSATED DRAIN. SAN T B REDUCER. 8. NEED 16" X 5" RELIEF DUCT IN MECH. ROOM, USE CORRECT TAPE ON FLUE JOINTS. |