Inspection Status: Correction Required
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/28/2000 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - NEED GAS METER TO TEST FURNACE OPERATION WILL NEED LICENSED CONTRACTOR TO VERIFY FURNACE OPERATION PRIOR TO FINAL |
| 04/28/2000 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
PARTIAL APPROVAL |
| 04/18/2000 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. NON LICENSED CONTRACTOR ON JOB! 2. DUCTWORK ON ROOF NOT INSULATED 3. CONTROL WIRING EXPOSED AND RUNNING WITH HIGH VOLTAGE 4. OLD FROZEN JOHNSTION ROOF TOP FURNACE NON LISTED VENT ASSEY. MISSING. |
| 04/18/2000 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |