Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/10/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ABS PLASTIC VENTS ON ROOF REQUIRES PROTECTION WITH LATEX PAINT 2) ELECTRIC SERVICE REQUIRES NON WATER BOND LABEL 3) KITCHEN COUNTER LEFT OF RANGE GREATER THAN 12" REQUIRES GFCI OUTLET |