Permit: T00CM01867

Parcel: 11306185F

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T00CM01867

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2000 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*
10/12/2000 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*/1. ELECTRIC SERVICE RISER MUST EXTEND A MINIMUM OF 12" BELOW GRADE. 2. ELECTRIC RISER NOT PROPERLY BONDED. SEE 1999 N. E. C. 250-94 "STANDARD LOCKNUTS OR BUSHING SHALL NOT BE THE SOLE MEANS FOR THE BONDING REQUIRED IN THIS SECTION" USE A BONDING RING OR BUSHING.