Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/14/2000 |
ELECTRIC - TEMPORARY SERVICE |
|
Approved |
IVRS - Inspection 0000* |
| 10/12/2000 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*/1. ELECTRIC SERVICE RISER MUST EXTEND A MINIMUM OF 12" BELOW GRADE. 2. ELECTRIC RISER NOT PROPERLY BONDED. SEE 1999 N. E. C. 250-94 "STANDARD LOCKNUTS OR BUSHING SHALL NOT BE THE SOLE MEANS FOR THE BONDING REQUIRED IN THIS SECTION" USE A BONDING RING OR BUSHING. |