Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T00CM01867
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2000 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection 0000* | |
| 10/12/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0999*/1. ELECTRIC SERVICE RISER MUST EXTEND A MINIMUM OF 12" BELOW GRADE. 2. ELECTRIC RISER NOT PROPERLY BONDED. SEE 1999 N. E. C. 250-94 "STANDARD LOCKNUTS OR BUSHING SHALL NOT BE THE SOLE MEANS FOR THE BONDING REQUIRED IN THIS SECTION" USE A BONDING RING OR BUSHING. |