Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/30/2002 |
MECHANICAL - ABOVE CEILING |
|
Approved |
|
| 07/29/2002 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
FAN COIL ACCESS NEEDS TO BE 30 X 30." 1.) WILL ACCEPT 24" X 30" IF FC CAN BE REMOVED. DO NOT ALLOW ANY BODY TO BLOCK CLEAR ACCESS. WHERE IS OVERFLOW PAN OR 2.) STEEL STRAY ON REF. LINES. TOTALLY ISOLATE RAW COPPER FROM STEEL. WRAP SUCTION LINES AT FAN COILS. 3.) COMB FIRE/SMOKE DAMPER IN CORRIDOR TRANSFER. |
| 06/21/2002 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* SUSPENDED DUCT PROGRESSING. |