Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/09/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/27/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/21/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*CANCEL BY BRET. |
| 08/15/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLAN NEED TO BE APPROVED BY CITY OF TUCSON PLAN CHECK 2.) NO BOND POSTED AT THIS TIME. 3.) PLUMBING BELOW SERVICE IS IN VIOLATION OF WORK SPACE 110-26. |
| 08/09/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0935* NO REVISED PLAN AT THIS TIME. SERVICE IS NOT INSTALLED AT THIS TIME AS PER PLANS NO BOND. A REFEE HAS BEEN ACCESSED. |
| 08/08/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*NEED REVISED PLAN ON SITE. |
| 08/07/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*CANCEL BY BRET. |
| 08/06/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLANS DO NOT REFLECT SERVICE INSTALLED, WIRE SIZE IS DIFFERENT. DISCONNECT LISTS FOR CLASS "R" FUSES ONLY AND CLASS "J" INSTALLED CANNOT FIND LISTING FOR LOOK AIR RATING. LEFT PAPER WORK FOR TEMP POWER REQUIREMENT. |
| 07/12/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*NEED TO POST BOND FOR TEMP POWER. |
| 07/11/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*BATHROOM WALLS OK TO COVER. |
| 07/10/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 07/01/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 06/26/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |