Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* PROVIDE LETTER VERIFYING SERIER RATING OF BREAKERS AND CORRECTED ONE LINE DIAGRAM |
|
| 06/20/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. NEED LETTER VERIFYING SERIES RATING OF BREAKERS 2. NEED CORRECTED ONE LINE DIAGRAM 3. BOND JUNCTION BOXES 250-96 | |
| 06/20/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |