Permit: T00CM01829

Parcel: 117084080


Addresses:

519 W 21ST ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/06/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* NEED PROPER CLEARANCE IN FRONT OF A/C 3'X30"
03/20/2001 ELECTRIC - FINAL Denied 1) STRAP #4 WIRE FROM SERVICE TO GAS LINES - TO FLOOR OR WALL 2) UNIT #3 CIRCUIT 13 YOU HAVE 1 #10 ON 25A 2POLE CIRCUIT-SHOULD BE ON 1 POLE CB-ALSO NOT MARKED IN PANEL SCHEDULE
3) A/C UNITS COMPRESSORS OUTSIDE REQUIRE 3' IN FRONT OF CLEAR TO GRADE ALSO NO TRIPPING HAZARDS. ALL UNITS TAPE WHITE AS HOT CONDUCTOR 4) WERE BOXES BEHIND FIXTURES IN BATHROOMS RELOCATED? BOX ALSO 5) UNIT #2 2 POLE 25A CB USED WHERE1 POLE SHOULD BE PANEL SCHEDULE INCORRECT #6 EMPTY, 16 EMPTY
6) BATHROOM LIGHTS INCORRECTLY MOUNTED NEED BOX BEHIND FIXTURES
03/16/2001 ELECTRIC - FINAL Denied 1) NEED TO HAVE HORDS INSTALLED 2) ONE HORD INSTALLED ROMEX WIRE COMPRESSED AGAINST WALL BOARD AND HOOD 3) NEED ROMEX CONNECTOR