Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/01/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*1.) OK ON REVERSE FEED TRANS PER RMS. OFFICE THUR 2.) DESION IN EQUIPMENT ROOM FOR TRANSFORMER OK PER FERNANDO GALVEZ MONRAD ENGINEERING EXTRA ON JOB. 3.) OK ON CHANGE OF FUSED DISION TO CV WITH SHUNT TRIP FOR X-RAY ON INSTALLERS APPROVAL THUR OFFICE. 4.) OK ON 1-3" RIGID & 3-2 RIGID CONDUIT IN X-RAY ROOM.
07/27/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1. 1/4" CONDUIT TO X-RAY RM 1.) CHANGE U.G. CONDUIT TO STEEL (SPEC. 2.) TRANSFORMER TO BE RATED PRIMARY 208 AND SECONDARY 480V. 3.) PLEASE CHECK ONE LINE FOR X-RAY DISCONNECT.
07/26/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*WALK APPROVED FOR X-RAY ROOM.
05/30/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
05/11/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* NOT READY
05/09/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* 1) ROUGH ALL WALLS AND CEILINGS EXCEPT DARK ROOM/CHEMICAL STORAGE AREA AND X-RAY ROOM 2) UNDER GROUND APPROVAL TO RECEPTION 3) GAS BOND X-OTHERMIC WELD APPROVED
05/04/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* COMPLETE SWITCH LEGS
05/02/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* ALL EXTERIOR PERIMETER WALLS
04/30/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245* 1) GAS BOND X-OTHERMIC WELD COVERED, UNDER SLAB NOT APPROVED
2) 2 1/2" AND 1 1/2" CONDUIT COVERED UNDER SLAB NOT APPROVED 3) PERIMETER EXTERIOR WALLS NOT APPROVED NEED WIRE PROTECTOR PLATES THROUGHOUT. ANYWHERE YOU ARE 1 1/4 OR LESS FROM FACE OF STREET