Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2001 | ELECTRIC - UNDERGROUND | Approved | ||
| 04/23/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK U.G. 1" PVC EAST & SOUTH 2 POLES (LIGHT) PAST ENTRY CROSSING AT COMMERCE CT. STREET. | |
| 03/15/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* OK UG SERVICE AREA ONLY | |
| 03/09/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* 4' WELD FOR GAS LINE NOT APPROVED | |
| 03/07/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* 1ST POLE OUT OF BLDG (SOUTH PARKING LOT) | |
| 02/22/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* INTERIOR UNDER GROUND PVC APPROVED(NOT FOR PATIENT CARE) 2" TO XRAY TRANSFORMER. WATER GROUNDING TO SERVICE APPROVED |
|
| 02/21/2001 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999* WIRING METHODS MUST COMPLY WITH ART 517-METALIC RACEWAYS FOR PATIEIT CORE. UFER GROUND WILL NEED ELEC. ENGINEER LETTER ON METHOD |