Permit: T00CM01798

Parcel: 13824101B


Addresses:

1510 W COMMERCE CT

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
08/08/2001 ELECTRIC - UNDERGROUND Approved
04/23/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*OK U.G. 1" PVC EAST & SOUTH 2 POLES (LIGHT) PAST ENTRY CROSSING AT COMMERCE CT. STREET.
03/15/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* OK UG SERVICE AREA ONLY
03/09/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* 4' WELD FOR GAS LINE NOT APPROVED
03/07/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* 1ST POLE OUT OF BLDG (SOUTH PARKING LOT)
02/22/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* INTERIOR UNDER GROUND PVC APPROVED(NOT FOR PATIENT CARE) 2" TO XRAY
TRANSFORMER. WATER GROUNDING TO SERVICE APPROVED
02/21/2001 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999* WIRING METHODS MUST COMPLY WITH ART 517-METALIC RACEWAYS FOR PATIEIT CORE. UFER GROUND WILL NEED ELEC. ENGINEER LETTER ON METHOD