Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/17/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) STRAP CONDENSATE DRAIN LINE TO BLOCKS & WALL 2.) GAS PIPE MISSING ROOF JACK. CORRECT & RECALL FOR FINAL |
| 06/22/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1)PROVIDE A ROOF JACK ON GAS PIPE PENETRATION THRU ROOF.2)HOOK UP CONDENSATE TO AC/1.3)PROVIDE OUTSIDE AIR VENTS ON AC-1.4)PROVIDE A FLASHING ON WATER LINE TO EVAP COOLER #1.5)RAISE VENTS TO 1' ABOVE EVAP COOLER #3.6)BLOCK AND CLAMP WATER LINE ON ROOF.COPPER CANNOT COME IN CONTACT WITH STEEL. |