Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/01/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) PLBG FINAL IS OK 2.) ALL CORRECTIONS HAVE BEEN MADE 3.) OK FOR C OF O. |
| 06/22/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MUST EXPOSE C.O. FOR SINKS AND INSTALL TOM CAPS OF FEMALE COUPLINGS WITH PLUG 2.) TRAP PRIMER MUST HAVE 1" AIR GAP IN FURNACE RM 3.) DOG WASH SINK TRAP IS HIGHER THAN OUTLET OF VENT 4.) WILL REQUIRE A BACKFLOW PREVENTER FOR DENTAL AREA SINK 5.) WATER HTR FLU VENT MUST HAVE 3 SHEET METAL SCREEN PER JOINT AND VENT CONNECTOR 6.) MUST STRAP DOWN EXPANSION TANK 7.) MUST PAINT ALL VENTS THRU ROOF 8.) MUST WRAP P-TEAP & SUPPLYS FOR H.C. LAV 9.) H.C. WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF RM 10.) MUST HAVE ALL BACKFLOW PREVENTERS TESTED |