Permit: T00CM01748

Parcel: 11716029A


Addresses:

103 E ALAMEDA ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM01748

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/04/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) SUPPORT ALL FIXTURES WITH SUPPORT WIRES AS REQUIRED 2.) LOOSE FITTINGS 3.) SUPPORT M/C CABLE AS PER CODE. 4.) DATA LAYING ON GRID. 5.) OPEN JUNCTION BOX ABOVE CEIL AND EXPOSED 277V CONDUCTORS. 6.) CONNECTION FITTINGS LOOSE USE PLATES THAT WILL SUPPORT FITTINGS.
10/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0920*IVR DOWN COULD NOT RETREVE MESSAGE NEED ACCESS TO ALL AREAS TO BE INSPECTED PLEASE PROVIDE STEP LADDER FOR INSPECTIONS NEED TO BE RECALLED BY 10-4-01
10/01/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
09/21/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935*
09/20/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
09/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935*
08/28/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
07/22/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*CANCEL BY FRANK
07/19/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
07/12/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
03/16/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) ATTACH FIXTURES TO GRID 2) STRAP FLEX CONDUIT AS PER CODE 3) ATTCH SUPPORT WIRES TO FIXTURES ROOM # WEST. OK SUBJECT TO INSP MANAGER DETERMINATION 4TH FLOOR
03/15/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) MISSING COVERS FOR POWER POLES 2) FILL ALL UNUSED OPENINGS 3) EXPOSED CONDUCTORS CAP AND INSTALL COVERS 4) SUPPORT CONDUIT AS PER CODE 5) INSTALL ALL TRAY COVERS 6) REVISE PANEL SCHEDULES
03/13/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*