Permit: T00CM01748

Parcel: 11716029A


Addresses:

103 E ALAMEDA ST


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T00CM01748

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
10/01/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*WE NEED TO HAVE ALL OCCUPIED AREAS READY FOR INSPECTIONS BY 10-3-01. OK DOMESTIC VIOLENCE & COURT ROOM #3.
09/23/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*1.) INSTALL EXIT SIGNS AS PER CODE. 2.) DATA ON GRID. 3.) OPEN CONDUCTORS LOOSE IN CEILING. A REFEE HAS BEEN ASSESSED.
09/21/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0935*
09/20/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*1.) DATA STILL LAYING ON GRID 2.) INSTALL EXIT LIGHTS AS PER CODE.
09/11/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0935*NO WORK PROGRESS IN WEST SIDE OF 1ST FLOOR A REFEE HAS BEEN ASSESSED AREA OCCUPIED WITHOUT APPROVAL.
08/31/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*PARTIAL APPROVED FRONT LOBBY.
08/28/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*1.) SUPPORT M/C CABLE AS PER CODE 2.) DATA LAYING ON GRID 3.) ATTACH FIXTURES TO GRID 4.) MISSING EXTENTION BOX AND JUNCTION BOX COVER 5.) FIXTURE WHIP TO BE CORRECTLY INSTALLED #118 CENTER LIGHT 6.) INSTAL CONDUCTORS UNDER SCREWS IN A CLOCKWISE DIRECTION ON RECEPTACLES 7.) INSTALL EXIT LIGHT AS PER CODE #120.
08/27/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*NEW LOBBY STUCCO ROUND COLUMN EAST.
08/14/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK ABOVE CEIL INFO ALCOVE
07/23/2001 ELECTRIC - ABOVE CEILING Partial Approval 1.) DATA STILL LAYING ON GRID 1ST FLOOR 2.) CK CONDUCTOR IDENTIFICATION ON FINAL.
07/19/2001 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*
07/12/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*1.) DATA LAYING ON GRID 2.) SUPPORT CONDUIT AND BOXES AS PER CODE 3.) ATTACH FIXTURES TO GRID 4.) SUPPORT FLEX CONDUIT AS PER CODE 5.) NEED SUPPORT WIRES ON EXIT SIGN 6.) SUPPORT M/C CABLE AS PER CODE. 4TH FLOOR: 1.) STRAP M/C CABLE AS PER CODE 2.) IDENTIFY CONDUCTORS IN FIXTURES AS TO VOLAGE 210-5 (C) 3.) PROVIDE MANUFACTURE INSTRUCTION FOR EMERGENCY LIGHTING TO VERIFY INSTALLATION 4.) INSTALL EMERGENCY LIGHTING AS PER PLAN. NOTE: A REFEE WILL BE ACCESS IF THESE DISCREPENCYS ARE NOT TAKEN CARE OF FOR FUTURE INSEPCTIONS.
07/10/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK LOBBY #100 WEST HALF
03/13/2001 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000* FINISH WORK FOR FINAL NEED BOND POSTED NEED LETTER TO INSPECTIONS MANAGER REGUARDING LIGHT FIXTURES ORDER STATUS
03/12/2001 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000* LEFT TEMP C OF O FORM WITH SUPER.