Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/19/2001 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*REMOVE VENT FROM CONDENSATE TRAP OR INSTALL DOWNSTREAM OF TRAP.SEE SEC. 310.3 1994 UMC CODE MODIFICATIONS.WILL CHECK ON FINAL. |
| 06/13/2001 |
MECHANICAL - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 06/12/2001 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1)STRAP FLEX DUCT UP OFF OF LIGHT IN ROOM AT END OF 1ST FLOOR.2)AIR HANDLER LOCATION NOT PER PLAN.PROVIDE ADEQUATE CLEARANCE TO SERVICE ACCESS PANEL AND FILTER.3)PIPE SECONDARY DRAIN TO A READILY VISIBLE LOCATION.4)PROVIDE HOSE CLAMPS ON CONSATE PUMP HOSE.5)PROVIDE A TRAP ON CONDENSATE DRAIN LINE. |