Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/09/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 06/13/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*OK CEILINGS 1ST FLOOR. |
| 06/12/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*NOTES. 1. INSTALL SUPPORT WIRES TO CEILING STRUCTURE FOR CAN LIGHTS # 9287 CITY ORD. 2. LAY IN FIXTURE (FLOURENCENT) REQUIRE 2 # 8 SCREWS OR RIVITS THRU GRID TO FIXTURE 410-16 NEC. 3. MC CABLE LONGER THAN 6' TO BE SUPPORTED PER 334-10 NEC. WITHIN 12" EACH TERMINATION & AT 6' INTERVALS. |