Inspection Status: Correction Required

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
05/05/2000 MECHANICAL - ABOVE CEILING Correction Required ADDTL COMMS - OK TO INSTALL CEILING TILES
05/04/2000 MECHANICAL - ABOVE CEILING Correction Required ADDTL COMMS - 1. SCREW DIFFUSERS TO GRID OR SUPPORT WITH STRAP OR WIRE 2. STRAP ALL FLEX DUCT OFF OF GRID AND LIGHTS MIN 1 1/2 WIDE METAL STRAP MIN 4 APART 3. ONE OFFICE HAS NO SUPPLY 4. INSTALL RETURN DIFFUSERS AS PER PLAN 5. RECALL WHEN CORRECTIONS HAVE BEEN MADE 5. BLANK OFF ABANDONED OPENINGS IN DUCT WITH METAL NOT TAPE
05/04/2000 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*