Inspection Status: Correction Required
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/05/2000 |
MECHANICAL - ABOVE CEILING |
|
Correction Required |
ADDTL COMMS - OK TO INSTALL CEILING TILES |
| 05/04/2000 |
MECHANICAL - ABOVE CEILING |
|
Correction Required |
ADDTL COMMS - 1. SCREW DIFFUSERS TO GRID OR SUPPORT WITH STRAP OR WIRE 2. STRAP ALL FLEX DUCT OFF OF GRID AND LIGHTS MIN 1 1/2 WIDE METAL STRAP MIN 4 APART 3. ONE OFFICE HAS NO SUPPLY 4. INSTALL RETURN DIFFUSERS AS PER PLAN 5. RECALL WHEN CORRECTIONS HAVE BEEN MADE 5. BLANK OFF ABANDONED OPENINGS IN DUCT WITH METAL NOT TAPE |
| 05/04/2000 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |