Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/05/2000 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - OK TO INSTALL CEILING TILES |
| 05/04/2000 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. SCREW DIFFUSERS TO GRID OR SUPPORT WITH STRAP OR WIRE 2. STRAP ALL FLEX DUCT OFF OF GRID AND LIGHTS MIN 1 1/2 WIDE METAL STRAP MIN. 4 APPART 3. ONE OFFICE HAS NO SUPPLY 4. INSTALL RETURN DIFFUSERS AS PER PLAN RECALL WHEN CORRECTIONS HAVE BEEN MADE 5. BLACK OFF ABANDONED OPENINGS IN DUCT WITH METAL, NOT TAPE. |
| 05/04/2000 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |