Permit: T00CM01704

Parcel: 126010520


Addresses:

920 N BELVEDERE AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/19/2000 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
1. ALL CORRECTIONS MADE SATISFACTORILY
2. WATER TEST OK
3. OK TO COVER WALLS
09/13/2000 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
ONLY WE AND TUB ON ONE UNIOT WATER TESTED TUB SHOE LEAKING
NO HUB BAND NOT APPROVED FOR CONNECTING ABS TO ABS
READ SECTION 1002.4 94" UPC OBTH UPSTAIRS TUBS NO APPROVED PLANS ON SIGHT
MAY NEED ADDITIONAL BRACES AND SUPPORTS
08/15/2000 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
MUST TEST WASTE AND VENT SYSTEM
TRAP ARM FOR TUB AND SHOWER HAS A OFFSET MAKEING IT A RUNNING TRAP
07/21/2000 PLUMBING - INTERMEDIATE Not ready for Inspection 1. PLEASE PROVIDE AS BUILD DRAWINGS NOT PER PLAN AT THIS TIME AND NO TEST
PLEASE SEE WATER HEATER LOCATION CODE VIOLATIONS ON REFIEF LINES TO WATER HEATERS TRAPPED WILL NEED TEST ABS AT TIME OF INSPECTION