Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2000 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 10/30/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* TYPE SJ CORD IS NOT APPROVED FOR PERMANENT WIRING CONCEALED IN WALLS. REPLACE FOR MOTOR AND A 14 FOR THE PUMP |
|
| 10/20/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | 10/20/00 OK WALLS, CEILINGS EXCEPT 2-GANG BOX FOR COOLER OVER FILLED CANNOT EXCEED 12# 12 CONDUCTORS* | |
| 10/17/2000 | ELECTRIC - INTERMEDIATE | Denied | THE ROMEX CABLE MUST HAVE A STAPLE NEAR WHERE IT ENTERS THE BOX. OK TO GROUP AND BUNDLE W/TIE AND STAPLE OFF. GROUND WIRES MUST BE CRIMPED TOGETHER WITH A CRIMP SLEEVE. TWISTING ONLY IS NOT ACCEPTABLE WIRE OUT OF WALL AT BATHROOM USE "BANG PLATES" TO PROTECT ROMEX IN STUDS WHERE THE HOLE IS CLOSER TO WALL THAN CENTER OF STUD RECALL WHEN CORRECTED |
|
| 10/09/2000 | ELECTRIC - INTERMEDIATE | Denied | IN PANEL NEUTRAL AND GROUND NOT TO BE TIED TOGETHER STAPLE ALL ROMEX WITHIN 12" OF BOXES MAKE UP ALL BOXES, TIE GORUNDS AND NEUTRALS PENISULA ELECTRICAL RANGE RECEPTACLE ON WRONG WALL NO PROVISIONS FOR RECEPTACLES AT END |
|
| 09/29/2000 | ELECTRIC - INTERMEDIATE | Denied | CONDUCTORS TO SHORT IN STAIRWAY LIGHT BOX NO PLANS ON SITE ASKED THE ELECTRICIAN SOME QUESTIONS ABOUT WIRING ON 09/28/00 HIS REPLY WAS, I DON'T KNOW I DIDN'T READ THE PLANS A REINSPECTION FEE IS ASSESTED |
|
| 09/27/2000 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* INSTALL SMOKE DETECTOR WIRING AND BOXES, MUST BE INTER CONNECTED. BATHROOM WALL LIGHT RANGE RECEPTACLE VERIFY VOLTAGE FOR BASE BOARD HEATERS AND WIRE ACCORDINGLY DO NOT SHARE 240 V CIRCUIT WITH 110 V RECEPTACLES |
|
| 09/13/2000 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
| 08/15/2000 | ELECTRIC - INTERMEDIATE | Denied |