Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/13/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/09/2001 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PARTIAL, ELEC; MECH;PLUMB;TEMP C O FOR FIRE OK. 1.) PROVIDE SPLASH BLOCKS @ ROOF DRAINS. |
| 07/10/2001 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) COMPLETE CANOPIES 2.) PROVIDE REBAR CAPS @ REBAR 3.) H.C. PARKING SIGNS 4.) STABILIZE EXTERIOR OUTLET BOX 5.0 STABILIZE EARTH AT TRANSFORMERS 6.) SPLASH BLOCKS AT ROOF DRAINS 7.) PROVIDE APPROVED FINAL INSPECTION AS NOTED ON LIST OF REQUIRED INSPECTION. |
| 07/06/2001 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) COMPLETE SITEWORK (GRADE,FLATWORK,PARKING PAVING ECT.) 2) THRESHOLDS 3.) GRAB BARS @H.C.TOILETS 4.) LANDINGS. 5.) CANOPY 6.) GLAZE OPENINGS IN DOORS 7.) EMERGENCY LTG. 8. APPROVED FINALS LISTED ON THE REQUIRED INSPECTION LIST. |
| 07/03/2001 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*COMPLETE SITE WORK, PROVIDE OTHER FINAL INSPECTION APPROVED ADDRESS AND NUMBER THE BUILDINS, I DIDNT GO INSIDE |