Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00CM01654
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
01/18/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/1. CLEAN OUTS REQUIRE APPROVED. THREADED CAPS AND TRIM TO GRADE. 2. OUTSIDE HOSE BIBS REQUIRE ANTI SIPHON VALUES. 3. NO ADDRESS ON HOUSE. 4. A/C CONDENSATE CANNOT BE DRILLED INTO SIDE OF WASTE VENT-USE SANITARY "T" WITH REDUCER FOR CONNECTION. 5. PAINT ABS AND PVC PIPES ON ROOF. 6. SUPPORT 3/4" GAS LINE AT 8' O.C. 7. NO POWER TO OUTSIDE GFCI OUTLETS. 8. ROOF OUTLETS AND DISCONNECTS CANNOT BE SUPPORTED BY SERVICING CONDUIT. 9. BATH GFCI HOT WHEN TRIPPED. 10. KITCHEN GFCI HOT WHEN TRIPPED. |