Permit: T00CM01637

Parcel: 12409141A


Addresses:

1749 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/14/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
08/23/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK ABOVE CEILING EXCEPT AS
NOTED AND ITEM #5.
08/20/2002 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*1.) CONDUIT FLEX & M/C CABLE TO BE SUPPORTED 348,351,334,300-11. 2.) FINISH CONDUIT RUNS OR MARK AS SPARES. 3.) FIXTURE TO BE ATTACHED TO GRID. 4.) TIGHTEN FITTING CONNECTIONS AT FIXTURES 5.) VERIFY WET/DAMP LOCATION FO RFIXTURES IN SHOWER AREAS.