Permit: T00CM01623

Parcel: 11307251A

Inspection Status: Correction Required

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
06/14/2000 ELECTRIC - TEMPORARY SERVICE Correction Required ADDTL COMMS - OK TEMP SERVICE
06/07/2000 ELECTRIC - TEMPORARY SERVICE Correction Required ADDTL COMMS - 1. COVER LISTING SHOW USE OF OTHER COMPONENT MAY VOID UL LISTING NEED FROM MFG LETTER STATING OK TO USE CUTLER-HAMMER WITH SQUARE D 2. PLASTIC BOX NOT LISTED FOR USE WITH METAL FLEX CONNECTOR AND FLEX
06/07/2000 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*
06/01/2000 ELECTRIC - TEMPORARY SERVICE Correction Required ADDTL COMMS - 1. PERMANENT ADDRESS LABEL AND UNIT LABELS 2. STRAP RISER 3. PROTECT EXPOSED ROMEX 4. SERVICE AND PANELS NEED TO BE SERIES RATED 5. USE BREAKER RECOMMENED BY MANUFACTURE
06/01/2000 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*